|
Floorheat Australia
In Screed & Thin Floor
Heating Specification
for Extended Off Peak, Domestic or Time of Use Tariff
(SCS2002)
IMPORTANT:
The Electrical Schedule details Electrical Loadings, Thermostat Types and
any other accessories such as Contactors or Time Switches included in the
quotation.
Please refer to Thermostat Specification.
The Electrical Schedule/s together with
this sheet must be passed on to your Electrical Contractor and all
other relevant Trades, before you accept any quotation. This will
enable them to furnish you with quotations for any additional work which
will be required. Failure to do so may result in extra costs being
incurred by you.
General
Any deviflex™/devimat™ quotation is
based on the following:
Unless stated elsewhere, In Screed
heating requires a 25mm thick screed bed over the heating cables.
A 6mm adhesive bed is recommend for devimat heating systems - or as per
manufacturers recommendations.
- When heating cables/mats are to be laid
directly on top of hard floors such as concrete, F/C Sheet or existing
tiled floors and no waterproofing membrane is being installed, the
heating will be fixed in place using either wire mesh, devifast™
fixing strips or glued directly to the floor.
 |
 |
|
Cables attached to devifast fixing strips and laid directly onto existing
concrete floor
|
Cables
attached to wire mesh and laid directly onto existing tiled
floor
|
|
|
Mat laid onto existing concrete floor
|
- Before heating cables/mats can be laid
on top of a Timber Floor, a layer of material similar to F/C sheeting
at least 1mm thick must be supplied and installed by others. The
heating cables/mats will then be laid on top, and fixed in place using
either of the methods listed above.
- When the heating system is to be
installed on a Timber Floor that is exposed underneath, insulation
must be installed to the underside of the floor.
- If the Heating system has been designed
as 'Thin Floor' for use under a Floating Timber Floor or Carpet,
heating cables should be covered by a 15mm screed bed, or if using
devimat a 6mm approved self levelling compound. All work must be done
in accordance with Adhesive and Floor Covering Manufactures
Recommendations.
- To avoid damage, the heating cables/mats
must be covered as soon as possible after they are installed. If wall
tiles are to be installed before the floor tiles e.g., Bathrooms, it
is recommended that the heating cables/mats be installed after the wall tiles
have been fixed.
Electrical
The quoted price includes the design,
supply and installation/fixing of the deviflex Heating Cables/devimats
only. All Thermostats, Contactors or Time Switches quoted are supplied
only, it is the responsibility of the Site Electrician to install and
connect them. Contactors are required for individual zones were the loads
are greater then the current carrying capacity of the thermostats supplied
(see Thermostat Specifications).
Important - Please Note! - Two empty
conduits must be installed as follows:-
- For
'Cold Tails' one 20mm (minimum)
empty conduit from the top of the finished concrete to switch or
thermostat position with a draw wire, must be provided for the 'cold
tails'.
|

|
|
Notice that for each
set of Cold Tails (each heating element) an extra conduit has been
installed. Also note that the sensor probe conduit is installed
between a cable loop. |
- If more than One heating element is
specified per zone, a separate empty 20mm conduit must be provide for each additional element. Please refer to the zones and
electrical loadings sheet supplied. See notes above for details.
- For Heating Mats, if more than Two
heating mats are specified per zone, an additional empty 20mm (min) conduit must be provided for every additional pair of heating mats
installed. See notes above for details.
- For Sensor Probes a separate empty
10mm-16mm conduit must be installed for the remote sensor probes. This
conduit will pass from the thermostat position down the wall, with a wide
radius bend into the screed. If possible the conduit will be situated 2m
in from the wall, the conduit end must always be accessible, this is to
allow for the sensor probe to be inserted or removed for servicing etc.
This conduit may be partially recessed/grooved into the sub-floor, to
allow a minimum screed thickness over the heating. For further information
regarding the sensor probes see the Thermostat
Specifications.
- The Site Electrical Contractor must
insert the sensor probe, (which is located in the Thermostat box) into the
conduit. The sensor must then be connected to the Thermostat. This
conduit must remain accessible for the future removal of the sensor probe,
if required for servicing.
- Contactors are supplied for individual
zones were the loads are greater then the current carrying capacity of the
thermostats supplied.
- All heating systems must be connected to
a 30 mA Residual Current Device.
Thermostat locations should be supplied in
writing, no less than 10 days before the installation of any cables is
required. If these are not received in time, we will position the cold
tails at our discretion. If any re-location of the cold tails is required,
this will be done on a 'do and charge' basis. A written work order is
required prior to commencement of any rectification work.
|